LIVE DEMO
Viewing as Full access — billing, integrations, financials & team security.
Start free trial
Start free trial
Fire risk assessment

Actions

The work every assessment asked for, and how far it has got.

Actions

Due: In the next 30 days

Clear

Export includes each action's description and notes. Describe groups, not individuals. Do not record names, flat numbers, or any person's health or mobility details.

Riverside House FRA-0012 · Issued 3 Oct 2026 · Assessor James Thornton 1 of 9 done
Action Priority Status Due Who owes it Record progress or open
Fit an intumescent strip and smoke seal to the head of the Flat 12 entrance doorset, matching those fitted to the jambs. A-02 · Second floor · Flat 12 entrance door High Open 31 Oct 2026 Riverside Housing Association
Fit an intumescent strip and smoke seal to the head of the Flat 27 entrance doorset, matching those fitted to the jambs. A-03 · Fourth floor · Flat 27 entrance door High Open 31 Oct 2026 Riverside Housing Association
Fit a tested intumescent pipe collar to the 110 mm soil pipe where it passes through the floor of the third-floor riser cupboard, installed by a competent fire stopping contractor. A-04 · Third floor · Third-floor riser cupboard soil pipe · 2 photos High In progress 31 Oct 2026 Riverside Housing Association

3 actions across 1 assessment.