Every item
Item list
| Ref | Item | Floor | Rating | Outcome | Reason | Recorded | Pin | Label |
|---|---|---|---|---|---|---|---|---|
| P-001 | Corridor C3 · Level 3, west wall Penetration seal | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 08:49 | Yes | Scanned |
| P-002 | Comms shaft · Level 3, shaft wall Penetration seal | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 08:58 | Yes | Scanned |
| P-003 | Corridor C4 · Level 3, ceiling void Cavity barrier | Level 3 | EI 30 | Clear | — | Ben Cooper 19 Oct 09:07 | Yes | Scanned |
| P-004 | Riser 2 · Level 3, east wall Penetration seal | Level 3 | EI 120 | Clear | — | Ben Cooper 19 Oct 09:16 | No | Scanned |
| P-005 | Corridor C4 · Level 3, east wall Linear joint | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 09:25 | Yes | Scanned |
| P-006 | Riser 2 · Level 3, north wall Penetration seal | Level 3 | EI 120 | Clear | — | Ben Cooper 19 Oct 09:34 | No | Scanned |
| P-007 | Corridor C3 · Level 3, west wall Penetration seal | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 09:43 | Yes | Scanned |
| P-008 | Comms shaft · Level 3, shaft wall Penetration seal | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 09:52 | No | Scanned |
| P-009 | Corridor C4 · Level 3, ceiling void Cavity barrier | Level 3 | EI 30 | Clear | — | Ben Cooper 19 Oct 10:01 | Yes | Scanned |
| P-010 | Riser 2 · Level 3, east wall Penetration seal | Level 3 | EI 120 | Clear | — | Ben Cooper 19 Oct 10:10 | Yes | Scanned |
| P-011 | Corridor C4 · Level 3, east wall Linear joint | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 10:19 | Yes | Scanned |
| P-012 | Riser 2 · Level 3, north wall Penetration seal | Level 3 | EI 120 | Clear | — | Ben Cooper 19 Oct 10:28 | Yes | Scanned |
| P-013 | Corridor C3 · Level 3, west wall Penetration seal | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 10:37 | Yes | Scanned |
| P-014 | Riser 2 · Level 3, east wall Penetration seal | Level 3 | EI 60 | Needs work | Annular gap out of tolerance | Ben Cooper 19 Oct 10:46 | Yes | Scanned |
| P-015 | Riser 2 · Level 3, riser wall Fire damper | Level 3 | EI 120 | Clear | — | Ben Cooper 19 Oct 10:55 | Yes | Scanned |
| P-016 | Riser 2 · Level 3, floor slab Penetration seal | Level 3 | EI 120 | Awaiting this visit | — | — | Yes | Printed |
| P-017 | Corridor C4 · Level 3, east wall Linear joint | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 11:04 | Yes | Scanned |
| P-018 | Comms shaft · Level 3, shaft wall Penetration seal | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 11:13 | Yes | Scanned |
| P-019 | Riser 2 · Level 3, south wall Penetration seal | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 11:22 | Yes | Scanned |
| P-020 | Corridor C3 · Level 3, west wall Penetration seal | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 11:31 | Yes | Code, not printed |
| P-021 | Riser 2 · Level 3, north wall (high level) Penetration seal | Level 3 | EI 120 | Clear | — | Ben Cooper 19 Oct 11:40 | Yes | Scanned |
| P-022 | Riser 2 · Level 3, west wall Penetration seal | Level 3 | EI 120 | Awaiting this visit | — | — | Yes | Printed |
| P-023 | Corridor C4 · Level 3, east wall Linear joint | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 11:49 | No | Scanned |
| P-024 | Riser 2 · Level 3, north wall Penetration seal | Level 3 | EI 120 | Clear | — | Ben Cooper 19 Oct 11:58 | No | Scanned |
| P-025 | Corridor C3 · Level 3, west wall Penetration seal | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 12:07 | No | Scanned |
| P-026 | Comms shaft · Level 3, shaft wall Penetration seal | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 12:16 | No | Scanned |
| P-027 | Corridor C3 · Level 3, cable tray Penetration seal | Level 3 | EI 60 | Needs work | Seal not continuous around the cable bundle | Ben Cooper 19 Oct 12:25 | No | Scanned |
| P-028 | Riser 2 · Level 3, east wall Penetration seal | Level 3 | EI 120 | Clear | — | Ben Cooper 19 Oct 12:34 | No | Scanned |
| P-029 | Corridor C3 · Level 3, ceiling void Linear joint | Level 3 | EI 60 | Not on site | Boxed in behind the new suspended ceiling — not visible | Ben Cooper 19 Oct 12:43 | No | Scanned |
| P-030 | Riser 2 · Level 3, north wall Penetration seal | Level 3 | EI 120 | Clear | — | Ben Cooper 19 Oct 12:52 | No | Scanned |
| P-031 | Riser 2 · Level 3, south wall (low level) Penetration seal | Level 3 | EI 120 | Awaiting this visit | — | — | No | Code, not printed |
| P-032 | Comms shaft · Level 3, floor slab Penetration seal | Level 3 | EI 120 | Awaiting this visit | — | — | No | Printed |
| P-033 | Corridor C4 · Level 3, ceiling void Cavity barrier | Level 3 | EI 30 | Clear | — | Ben Cooper 19 Oct 13:01 | No | Scanned |
| P-034 | Riser 2 · Level 3, east wall Penetration seal | Level 3 | EI 120 | Clear | — | Ben Cooper 19 Oct 13:10 | No | Scanned |
| P-035 | Corridor C4 · Level 3, east wall Linear joint | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 13:19 | No | Scanned |
| P-036 | Riser 2 · Level 3, north wall Penetration seal | Level 3 | EI 120 | Clear | — | Ben Cooper 19 Oct 13:28 | No | Scanned |
| P-037 | Corridor C3 · Level 3, west wall Penetration seal | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 13:37 | No | Scanned |
| P-038 | Corridor C4 · Level 3, east wall Penetration seal | Level 3 | EI 60 | Needs work | Foam used in place of a tested sealant | Ben Cooper 19 Oct 13:46 | No | Scanned |
| P-039 | Corridor C4 · Level 3, ceiling void Cavity barrier | Level 3 | EI 30 | Clear | — | Ben Cooper 19 Oct 13:55 | No | Scanned |
| P-040 | Riser 2 · Level 3, east wall Penetration seal | Level 3 | EI 120 | Clear | — | Ben Cooper 19 Oct 14:04 | No | Code, not printed |
| P-041 | Corridor C4 · Level 3, east wall Linear joint | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 14:13 | No | Code, not printed |
| P-042 | Riser 2 · Level 3, north wall Penetration seal | Level 3 | EI 120 | Clear | — | Ben Cooper 19 Oct 14:22 | No | Code, not printed |
| P-043 | Corridor C3 · Level 3, west wall Penetration seal | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 14:31 | No | Scanned |
| P-044 | Corridor C4 · Level 3, head of wall Linear joint | Level 3 | EI 60 | Needs work | Joint open along 600mm at the deflection head | Ben Cooper 19 Oct 14:40 | No | Scanned |
| P-045 | Corridor C4 · Level 3, ceiling void Cavity barrier | Level 3 | EI 30 | Clear | — | Ben Cooper 19 Oct 14:49 | No | Scanned |
| P-046 | Riser 2 · Level 3, east wall Penetration seal | Level 3 | EI 120 | Clear | — | Ben Cooper 19 Oct 14:58 | No | Scanned |
| P-047 | Corridor C4 · Level 3, east wall Linear joint | Level 3 | EI 60 | Clear | — | Ben Cooper 19 Oct 15:07 | No | Scanned |
| P-048 | Riser 2 · Level 3, north wall Penetration seal | Level 3 | EI 120 | Clear | — | Ben Cooper 19 Oct 15:16 | No | Scanned |